Multifunctional Systems
TRILOGY
Series
45÷210KW

MAIN FEATURES:

  • Wide range of aggregates including 15 models, 3 versions.
  • Average step of 25 kW.
  • EER up to 3.24.
  • COP up to 3.73.
  • ESEER up to 4.53.
  • Scroll compressors.
  • Single refrigeration circuit.
  • Refrigerant charge - R410A.
  • Plate heat exchanger.
  • Axial EC fans.
  • Single air circuit.
  • Electronic expansion valve.
  • Suitable for indoor installation.
Features

WORKING LIMITS IN COOLING MODE:

  • Chilled water outlet temperature: -10÷15°C
  • Ambient temperature: -12÷18°C

 

WORKING LIMITS IN HEATING MODE:

  • Hot water outlet temperature: 30÷60°C
  • Ambient temperature: -10÷35°C

 

ADVANTAGES:

  • IDEA® dynamic defrost monitoring system.
  • Pumping groups.
  • Noise-canceling kit.
  • EC fans with high efficiency.
  • Easy maintenance.
  • Eurovent certification.

 

POWER SUPPLY: 400/3/50 + N.

 

COMPONENTS:

  • FRAMEWORK: steel with protective epoxy coating; color: RAL 9002.
  • COMPRESSORS: scroll compressors; 2-pole 3-phase electric motor with direct start function; phases control relay; crankcase heater; thermal protection of the motor via temperature sensors; anti-vibration rubber supports.
  • EVAPORATOR: brazed plate heat exchanger in stainless steel; polyurethane insulation; water temperature sensors at the inlet and outlet; differential pressure switch; antifreeze heater.
  • REFRIGERATING CIRCUIT: reversible valve for inversion on the refrigerant circuit; electronic expansion valves; sight glass; service valve on the gas and suction line of the compressor; check valves; solenoid valve on the liquid line; safety valve on the line of low and high pressure; oil purification and regeneration system; a drop catcher on the suction line; IDEA® dynamic defrost monitoring system.
  • ELECTRICAL PANEL: main switch with safety lock; magnetothermic switches or fuses for compressors, fans or water pumps; contactors for compressors;
  • CONTROL SYSTEM: MP.COM microprocessor control with graphical display; volt-free contact as an element of the general emergency warning system; real clock timer; flash memory; components hour-meter; a password-protected menu; LAN connection.