Water to water indoor unit for the production of chilled/hot water with hermetic rotary Scroll compressors, braze-welded plate-type exchanger and electronic expansion valve. Basement and frame in hot-galvanised shaped sheet steel with a suitable thickness. All parts polyester-powder painted to assure total weather resistance, RAL 7035. The range includes the single-circuit two-compressor versions and thedual circuit four-compressor versions.
Controls
Electronic control W3000TE
The brand new W3000TE controller offers advanced functions and algorithms.
The keypad W3000 Compact, as standard equipment, features function controls and a complete LCD display for viewing data and
activating the unit, via a multilevel menu, with settable display language.
The controller provides water temperature control for the heating systems, cooling systems (only for reversible units), as well as for domestic hot water (only for reversible units). These different temperatures are managed automatically based on the different conditions in which the system operates, with the possibility to assign specific levels of priority to domestic hot water production, depending on the needs of the application.
The regulation is based on the exclusive QuickMind algorithm, including self-adaptive control logics, beneficial in low water content systems. As alternatives the proportional- or proportional- integral regulations are also available.
Diagnostics include complete alarm management, with “blackbox” functions (via PC) and alarm log (display or PC) for best analysis of unit be haviour. For systems made up of multiple units, differentiated device management means just a certain portion of the capacity installed can be dedicated to domestic water production, in this way ensuring more efficient energy distribution and, at the same time, guaranteeing simultaneous water delivery to the different distribution systems. The built-in clock can be used to create an operating profile containing up to 4 typical days and 10 time bands, essential for efficient programming of energy production and fundamental for managing the Legionella prevention cycles. Available time bands also for DHW production.
Supervision is available with different options, using proprietary devices or by integration into third party systems using ModBus, BACnet, BACnet-over-IP and Echelon LonWorks protocols.
A dedicated wall-mounted keypad can be used for remote control of all the functions.
Optionally (VPF package), capacity modulation can be integrated with hydraulic flow modulation, thanks to inverter-driven pumps and to specific resources for the hydraulic circuit.
Characteristics
VERSION
- Basic
CONFIGURATIONS
H Function with heat pump, reversible on hydraulic side
HIGH EFFICIENCY
Very high efficiency at full and partial load, at the highest market levels, thanks to the adopted technological solutions. These units ensure low operating costs and therefore a quick payback time.
ErP READY
The highest level of efficiency at part load can meet and exceed the minimum seasonal efficiency for heating, SCOP (only for reversible units) and for cooling, SEER, according with the eco-sustainable design requirements for all products using energy. The units already comply with the minimum seasonal energy efficiency requirements that will start from 2021.
VARIBLE PRIMARY FLOW (OPTION)
Energy saving due to variable pump speed management based on load demand and the variable flow assures the functioning of the units also with critical working conditions. VPF (Variable Primary Flow) available for sizes 0604-1204.
EXTREMELY SILENT OPERATION
Extremely silent operation together with high efficiency, tank to dedicated acoustic devices and a precise design for the choice of the components.
INTEGRATED CONDENSATION´S CONTROL
The electronics of the units manages the most suitable condensing control for each type of application: two or three-way modulating valve and 0-10V signal for variable speed driven pumps.
TOTAL VERSATILITY
Climaveneta has designed the NX-W units with a range of integral accessories in mind for operation with total water loss (well, water bed, etc.), dry cooler or cooling tower and suitable for geothermal application so as to satisfy all service system and installation requirements.
ELECTRONIC EXPANSION VALVE SUPPLIED STANDARD
The use of the electronic expansion valve generates considerable benefits, especially in cases of variable demand and at different working conditions. It guaranteed energy saving due to efficiency optimization in various different working conditions. The electronic thermostatic valve allows you to obtain speed in reaching machine stability and an extension of the operating limits.
Accessory
- Touch Screen visual display
- Set-up for remote connectivity with ModBus/Echelon protocol cards
- Outside air temperature probe for plant water set point compensation.
- Integral acoustical enclosure (type base)
- Thicker soundproofing cladding
- VPF (Variable Primary Flow) system
- Condensing control device: two or three-way modulating pressure-controlled valve and inverter on pumps