Outdoor heat pump for the production of chilled/hot water with hermetic rotary Scroll compressors, ozone-friendly refrigerant R410A, axial-flow fans, shell and tubes exchanger and electronic expansion valve. The range is composed by units equipped with four, six and eight compressors in multi-circuit configuration.
Controls
W3000SE Compact
The W3000SE Compact controller offers advanced functions and algorithms.
The keypad features an easy-to-use interface and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable language setting.
The regulation is based on the exclusive QuickMind algorithm, including self-adaptive control logics, beneficial in low water content systems.
As alternatives the proportional- or proportional-integral regulations are also available.
The diagnostics includes a complete alarm management, with the "black-box" and alarm logging functions for enhanced analysis of the unit operation.
For multiple units’ systems, the regulation of the resources, via optional proprietary devices, can be implemented. Energy metering, for both consumption and capacity, can also be developed. Supervision can be easily developed via proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks.
Compatibility with the remote keyboard managing up to 10 units.
Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour belts).
The defrost adopts a proprietary self-adaptive logic, which features the monitoring of numerous operational parameters. This allows to reduce the number and duration of the defrost cycles, with a benefit for the overall energy efficiency.
Характеристики
VERSION
B Basic
SL Super-low noise version
CA High efficiency version
CONFIGURATIONS
- Basic function
D Partial condensing heat recovery function
REFRIGERANT GAS R410A
The use of R410A allowed to achive better energy efficiencies with environment full respect (ODP = 0)
EXCHANGER
The shell and tube exchanger allows to achieve the highest flexibility on the unit’s installation, keeping the efficiency at the maximum level. For this reason, NECS-N represents the best choice for all the hydronic application on the residential, commercial and industrial markets.
ELECTRONIC EXPANSION VALVE SUPPLIED STANDARD
The use of the electronic expansion valve generates considerable benefits, especially in cases of variable demand and different external conditions. It was introduced into these units as a result of accurate design choices concerning the cooling circuit and the optimisation of operation in various different working conditions
INTEGRATED HYDRONIC GROUP
The optional built-in hydronic module already contains the main water circuit components; it is available with single or twin in-line, for achieving both low or high head.
Accessory
- Soft starters
- Set-up for remote connectivity with ModBus, Echelon LonTalk, Bacnet protocol board
- Remote control keyboard (distance to 200m and to 500m)
- LT kit for extending the operating limits in heat pump mode down to -10 °C (/SL-CA versions) and -12 °C (/CA versions)