Air Cooled Free-Cooling Liquid
EAGLE FREE
Series
R410A... 63÷311KW

MAIN FEATURES:

  • Wide range of aggregates including 17 models.
  • Average step of 20 kW.
  • EER up to 2.96.
  • ESEER up to 3.85.
  • Scroll compressors.
  • Refrigerant type - R410A.
  • Single or double refrigeration circuit.
  • Plate heat exchangers.
  • EC Axial fans.
  • Single air circuit.
  • Suitable for indoor installation.
Features

WORKING LIMITS IN COOLING MODE:

  • Chilled water outlet temperature: 4 ÷ 15 °C
  • Ambient temperature:  -10 ÷ 45 °C

WORKING LIMITS IN FREE-COOLING MODE:

  • Chilled water outlet temperature (minimum): -15 °C
  • Ambient temperature (minimum): -20 °C

 

ADVANTAGES:

  • Units are equipped with: two scroll compressors for each refrigerant circuit.
  • Units with one or two refrigeration circuits.
  • Highly efficient EC fans.
  • Ability to install: noise suppression kit, pumping group, heat recovery system.
  • Free-cooling system.
  • Easy maintenance.
  • Eurovent certification.

 

POWER SUPPLY: 400/3/50.

 

COMPONENTS:

  • FRAMEWORK (base, self supporting frame and panelling ): steel with protective epoxy coating; color: RAL 9002.
  • COMPRESSOR: hermetic scroll compressors optimized for the use of R410A refrigerant; thermal protection of motor via temperature sensors; phases control relay, rubber supports.
  • EVAPORATOR: brazed plate heat exchanger is made of stainless steel with polyurethane insulation; equipped with temperature sensors, a differential switch helping to control water pressure and with antifreeze heater.
  • CONDENSING AND FREE-COOLING COIL: copper tubes with aluminum fins, which increase the heat exchange of the system; Characterized by: maximum capacity relative to the size of the heat exchanger; reduced air consumption; frame made of galvanized steel; ambient air temperature sensor.
  • FANS: fans with sickle-shaped blades; equipped with an AC motor rotor.
  • CONTROL SYSTEM: MP.COM microprocessor control with graphical display; volt-free contact for the emergency warning system; components hour-meter; a password-protected menu; LAN connection.