Air Cooled Free-Cooling Liquid
GLIDER EVO FREE CLA
Series
R134a... 288 ÷1445KW

MAIN FEATURES:

  • Wide range of aggregates including 24 models.
  • Average step 50 kW
  • EER up to 3.34.
  • ESEER up to 3.83.
  • Two-screw compressors.
  • Chargeable refrigerant - R134A.
  • Double refrigeration circuit.
  • Shell-and-tube evaporator.
  • AC Axial fans.
  • Double air circuit.
  • Electronic expansion valve.
  • Suitable for outdoor installation.
Features

WORKING LIMITS IN COOLING MODE:

  • Chilled water outlet temperature: -10 ÷ 15 °C
  • Ambient temperature:  -20 ÷ 45 °C

WORKING LIMITS IN FREE-COOLING MODE:

  • Chilled water outlet temperature (minimum): -15 °C
  • Ambient temperature (minimum): -20 °C

 

ADVANTAGES:

  • Glycol-free system.
  • High rates of EER and ESEER.
  • “A” class energy efficiency
  • Ability to install: noise-suppressing or super-noise-suppressing kits, pumping group, heat recovery system, high-efficiency EC fans.
  • Eurovent certification.

 

POWER SUPPLY: 400/3/50.

 

COMPONENTS:

  • FRAMEWORK (base, self supporting frame and panelling ): steel with protective epoxy coating; color: RAL 9002.
  • COMPRESSOR: two-screw semi-hermetic compressors, optimized for R134a refrigerant; thermal protection of the motor via temperature sensors; terminal box with IP54 enclosure class; the oil level indicator and the replaceable cartridge of the oil filter.
  • EVAPORATOR: shell-and-tube evaporator; tubes with a helical rifled internal surface; polyurethane thermal insulation; shell, header, tube sheets, made of carbon steel, copper tubes; equipped with temperature sensors for monitoring water pressure, and with antifreeze heater.
  • CONDENSING AND FREE-COOLING COIL: copper tubes with aluminum fins which increase heat exchange of system and reduce the amount of refrigerant;
  • Characterized by: the minimum volume of refrigerant needed; reduced air consumption required for heat exchange; presence of an ambient temperature sensor.
  • FANS: fans with sickle-shaped blades; equipped with a rotary AC motor; stepless variable speed with phase-cut electronic controller for condensing pressure and free-cooling control
  • CONTROL SYSTEM: MP.COM microprocessor control with graphical display; volt-free contact for emergency warning system; work timer components; a password-protected menu; LAN connection.