Features
Mycond three-way valves are used to control delivery of fan coil units by opening/closing the flow passage for the heat-carrying and coolant fluid. The valve is provided with a return spring. The valve is normally closed. Once the thermal drive is powered up, the valve opens. When the actual indoor air temperature reaches the set parameters, the thermostat of the fan coil unit cuts off the power supply to the thermal drive of the valve. This cuts off the supply of heat-carrying and coolant fluid to the fan coil unit. By sequential closing/opening of the valve, constant air temperature is maintained. The drive is attached to the valve by a threaded joint. After the valve is fixed on the main pipeline, the drive can be mounted on the valve. It is advisable to mount the valve on the main pipeline using 1/2″ and 3/4″ flexible joints.
Valve housing |
brass CW617N |
---|---|
Valve rod |
stainless steel (AISI 302) |
Leak-proof insert |
EPOM rubber |
Connection |
1/2 (DN15); 3/4 (DN20) |
Kvs |
2.8 |
Kvs By-pass |
1.8 |
Valve rod stroke |
2.5 mm |
Weight |
400 g |
Dimensions (H x W x D) |
112,5 х 30 х 56 mm |